An Application of PSS®SINCAL/NETOMAC for Electromagnetic Transient Studies
Normal switching
maneuvers in high voltage systems cause fast transient overvoltages
and overcurrents which may be dangerously high. These electromagnetic
transients (EMT) depend on a series of system characteristics
such as the configuration of transmission lines and cables, transformer
design, existence of capacitor banks, and other parameters. In
order to predict the transients and to properly dimension the
power system’s insulation characteristics, engineers simulate
the electromagnetic transients using computer programs. These
programs numerically solve a large number of algebraic and differential
equations with partial and total derivatives with linear and non-linear
parameters. PSS®SINCAL can be used to perform such simulations
by running the program system PSS®NETOMAC in the background.
In addition
to other well-known features of PSS®SINCAL, the main advantages
of using this program for EMT studies are these: (1) relatively
simple migration of data from PSS®E load-flow and sequence
data files including the standard one-line diagram; (2) the entire
transmission network or a large portion of it can be simulated
with a minimal use of equivalents, for a more accurate representation;
(3) the instantaneous interface between the simulation window
and the graphic results window eases the engineering analysis;
(4) when desired, results may be stored in IEEE COMTRADE format
for subsequent analysis using SIGRA® or sharing with other
applications; and (5) instantaneous connection of the graphics
with the document Windows® environment for fast report writing.
The Houston
office of Siemens PTI recently finished a study to determine the
switching transients associated with the 500/220/110kV transmission
system of Afghanistan. As a result of steady-state studies using
PSS®E, this system was found to require reactive compensation
at several locations of the transmission network, including several
110kV and 220kV capacitor banks, and several 500kV and 220kV reactors.
The transient electromagnetic study mainly included: (a) switching
of capacitor banks and preliminary limiting inductor calculations;
(b) line energization; (c) transformer energization; (d) reactor
energization; and (e) single-phase-to-ground fault with three-phase
clearing.
The study
was carried out using the combined simulation and graphic capabilities
of PSS®SINCAL, which allowed a large number of simulations
in a relatively short period of time, automatically producing
the ready-to-insert standard graphic results used to create the
written report. Figure 1 shows an example of the results obtained
in this study, of one simulation of a single-phase-to-ground fault
with three-phase clearing. This report was delivered on-time/on-budget
to the customer in late May 2008.
Figure 1 - Simulation Example
Download
document as .pdf
| Siemens Power Transmission
& Distribution, Inc., Power Technologies International
400 State Street | P.O. Box 1058 | Schenectady,
NY 12301-1058
Privacy
& Legal |
|