Modeling of Two-Winding Voltage Regulating Transformers for
Positive Sequence Load Flow Analysis in PSS®E
Introduction
Electrical transformers are important components in transmission
and distribution power systems; they make possible the transfer
of MWs and Mvars between networks operating at various voltage
levels. The modeling of these power system components in the steady-state
analysis of electrical networks is critical since incorrect data
for their positive sequence winding leakage impedance, magnetizing
branch admittance, off-nominal turn ratio, number of tap positions,
tap range or voltage control band, may lead to erroneous results
in the verification of voltage control schemes, assessment of
transmission losses and computation of system var flows.
The main
objective of this article is to assist PSS®E users
with a guide for entering electrical transformer data for the
positive sequence model of the electrical network with a minimum
of effort and minimal causes for errors.
Notes/suggestions
for entering each of the required model variables follow, along
with an example of a two-winding voltage regulating transformer
modeled in PSS®E.
Model
Data Requirements
The per-phase positive sequence network model used by PSS®E
for three-phase two-winding transformers or three-phase banks
of three identical single-phase two-winding transformers is shown
in Figure 1 below. This model allows the modeling of the transformer
magnetizing admittance,
Ym = Gh+e -j Bm, that is often
neglected on the I-side (winding 1) of the transformer and allows
the modeling of the between windings 1-2 equivalent leakage impedance
Zeq= req +j xeq. One of the many
features of PSS®E is that the user does not have
to calculate the winding equivalent leakage impedance, magnetizing
branch admittance, effective off-nominal transformer tap, tap
step and tap limits; these calculations are done within PSS®E.

Figure
1 - PSS®E Two-Winding Transformer Model
As users create their transformer data records, PSS®E’s
flexibility becomes apparent. Each of the required model variables
is discussed below.
- Equivalent
winding leakage impedance Zeq:
- in
per unit on a system three-phase apparent power MVA base—SBASE,
usually 100 MVA—and windings 1 and 2 phase-to-phase
rated voltages for fixed tap transformers and nominal tap
for transformers fitted with either under-load or off-load
taps (t10 = t20= 1.0 per unit or t10
=VB1 kV and t20= VB2 kV) – Impedance
code CZ=1.
- in
per unit on a winding 1-2 three-phase apparent power MVA
base—SB1-2, usually the ONAN rating—and windings
1 and 2 phase-to-phase rated voltages (VB1 and VB2) for
fixed tap transformers and nominal tap for transformers
fitted with either under-load or off-load taps (t10
= t20= 1.0 per unit or t10 =VB1 kV
and t20= VB2 kV) – Impedance code
CZ=2.
- short-circuit
test three-phase full-load winding copper losses (Wsc)
in Watts and the impedance voltage magnitude or equivalent
winding leakage impedance magnitude in per unit on a winding
1-2 three-phase apparent power MVA base—SB1-2, usually
the ONAN rating?and windings 1 and 2 phase-to-phase rated
voltages (VB1 and VB2) for fixed tap transformers and nominal
tap for transformers fitted with either under-load or off-load
taps (t10 = t20= 1.0 per unit or t10
= VB1 kV and t20= VB2 kV) – Impedance
code CZ=3.
- Transformer
magnetizing admittance Ym:
- in
per unit on a system three-phase apparent power MVA base—SBASE,
usually 100 MVA—and winding 1 phase-to-phase bus voltage
base – Magnetizing Admittance code CM=1.
- open
circuit test three-phase no-load core losses (Wnl)
in Watts and the no-load excitation current magnitude or
the magnetizing admittance magnitude in per unit on a winding
1-2 three-phase apparent power MVA base?SB1-2, usually the
ONAN rating?and windings 1 phase-to-phase rated voltage
(VB1) for fixed tap transformers and nominal tap for transformers
fitted with either under-load or off-load taps (t10
= 1.0 per unit or t10 =VB1 kV) –
Magnetizing Admittance code CM=2.
-
Winding 1-2 three-phase apparent power MVA (SB1-2):
This
is the three-phase apparent power MVA used in the normalization
(per unit representation) of the winding leakage impedance Zeq.
Use of the transformer’s three-phase nameplate rating—which
is usually the ONAN rating—is strongly recommended; however,
any other three-phase apparent power base can be used. (As a matter
of fact, all of the two-winding transformer legacy data up to
version 26 of PSS®E is expressed on a system three-phase
apparent power base—most likely 100 MVA—and a system
bus voltage base.) System bus voltage base refers to the bus phase-to-phase
voltage base in kV when specifying the buses to which the terminals
of the two-winding transformer are connected. Note that when specifying
base quantities for two-winding transformers you must specify
an apparent power base and two voltage base values; one for winding
1 (NOMV1) and another for winding 2 (NOMV2).
- Winding
nominal voltage (NOMV1, NOMV2):
A nominal
phase-to-phase voltage—usually
the phase-to-phase rated or nominal tap winding voltage—should
be entered for winding 1 and winding 2. The nominal voltage for
winding 1 is used in the conversion of the no-load test data expressed
on a winding three-phase apparent power MVA and winding nominal
(rated) phase-to-phase voltage base on a system three-phase apparent
power MVA and system bus voltage base. The nominal voltage for
winding 2 is used in PSS®E version 31 and newer
versions to convert the per unit tap values on a winding voltage
base (that is, as they appear on the transformer test report and
nameplate data) to per unit tap values on system bus voltage base.
The default value for these two data entry points is 0.0 kV, which
means that the winding nominal voltage is equal to the voltage
base of the bus to which the transformer is connected. For PSS®E
version 30 and earlier versions the nominal voltage for winding
2 is not used in any calculations related to the winding leakage
impedance, per unit tap value, or performance of a transformer
unit.
- Number
of tap positions in winding 1 (NTP1):
PSS®E
assumes that the nominal tap position is located midway the tap
range: (NTP1+1)/2. PSS®E also assumes that the
winding 1 tap step is constant: t1=
TSTEP1= (Rmax – Rmin)/(NTP1-1).
- Winding
off-nominal taps (WINDV1 and WINDV2):
- Automatic
adjustable taps (ULTCs) will be associated with winding
1 (t1), and manually or off-load adjustable taps
will be associated with winding 2 (t2). These
taps may be specified in:
- per
unit on bus “I” and “J” phase-to-phase
system voltage – Winding code CW=1.
- kV
winding 1 and 2 phase-to-phase voltages –
Winding code CW=2.
- per
unit on winding 1 and 2 phase-to-phase rated voltages –
Winding code CW=3.
- Tap
limits (Rmax, Rmin):
These apply
only to taps in winding 1 and they define the winding tap range.
Two values are used for these limits Rmax for the upper limit
and Rmin for the lower limit. These tap limits may be specified
in:
- per
unit on bus “I” and “J” phase-to-phase
system voltage – Winding code CW=1.
- kV
winding 1 and 2 phase-to-phase voltages – Winding
code CW=2.
- per
unit on winding 1 and 2 phase-to-phase rated voltages –
Winding code CW=3.
- Winding
1-2 voltage phase angle or winding 1 phase shift angle (
12= 1
– 2):
The relative
phase angle between winding 1 and winding 2 may be specified in
the transformer data record. This phase shift angle is measured
in electrical degrees and is assumed to be positive when winding
1 phase voltage leads winding 2 phase voltage, and to be negative
when winding 1 phase voltage lags winding 2 phase voltage. For
example, if winding 1 (wye-grounded connected) lags winding 2
(delta connected) by 30° (Ygd11 in the IEC notation), then
the angle 12=
-30°. In a future newsletter, we will address the modeling
in PSS®E of phase-shifter transformers.
- Transformer
control band (Vmax, Vmin):
The upper
and lower limits of voltage regulating transformers are specified
in the entries Vmax and Vmin, respectively. These limits may be
expressed in either kV or per unit when the transformer control
mode is 1 (i.e., voltage control) or in Mvar flow into the terminals
of winding 1 when the transformer control mode is 2 (i.e., reactive
power flow control). When the upper and lower voltage limits are
expressed in per unit, the voltage base is the bus voltage base
of the bus bar when local or it is the bus voltage at the remote
bus where voltage is to be controlled. It is important to keep
in mind that the control band width (Vmax – Vmin) must be
equal to or greater than two times the transformer’s tap
step TSTEP1. This will guarantee that when the tap adjustment
option is used in a load flow solution, and the control mode is
1, the tap solution will not oscillate between tap limits. When
the control mode is 1, the default values are: for the upper limit,
1.1 per unit (or 1.1*bus voltage base in kV) and, for the lower
limit, 0.9 per unit (or 0.9*bus voltage base in kV). There are
no default values allowed for control mode 2.
- Transformer
control mode (COD1):
Voltage regulating
transformers in PSS®E can be modeled in three
control modes:
- mode
0, the default mode, where taps in both windings are set manually
and are fixed
- mode
1, voltage control mode, where winding 1 tap is adjusted when
the load flow solution option “tap adjustment”
is selected
- mode
2, Mvar control mode, where winding 1 tap is adjusted when
the load flow solution option “tap adjustment”
is selected.
An
Important Note:
It is important to note that the transformer model in PSS®E
automatically adjusts the winding leakage impedance when there
is mismatch between the winding base voltage (NOMV1 and NOMV2)
and the base voltage of the bus where transformer terminals are
connected. Figure 2 shows that when the winding 2 base voltage
is not the same as its bus voltage base, PSS®E
will automatically multiply the specified winding leakage impedance
in per unit on a winding apparent power base and a winding voltage
base by the square of the winding 2 off-nominal winding turns
ratio (t2)2 as this impedance is referred
to the bus “J” side – see Figure 1. If the winding
1 base voltage is also not the same as its bus voltage base, PSS®E
will adjust the transformer winding leakage impedance using the
winding 1 off-nominal winding turns ratio t1. These off-nominal
winding turn ratios, t1 and t2, are specified
by the user as:
t1
= winding 1 voltage/ bus “I” base voltage when given
in per unit
= winding 1 base voltage when given in kV
t2
= winding 2 voltage/ bus “J” base voltage when given
in per unit
= winding 2 base voltage when given in kV
When the
winding code is 3, taps are specified in per unit on a winding
voltage base and PSS®E will automatically take
care of the voltage base mismatch by multiplying the winding off-nominal
tap by the factor (winding base voltage/bus base voltage).
The winding
1 tap limits Rmax and Rmin must also be adjusted when they are
specified in per unit on a bus “I” voltage base.
All computations
carried out by PSS®E are performed in per unit
on a system apparent power base and bus voltage base.

Figure
2 - Standard PSS®E Two-Winding Transformer Circuit
Numerical
Example
A numerical example follows to show how a two-winding voltage
regulating transformer is modeled and how the model data is entered
in PSS®E.
For our example
we will use a two-winding three-phase transformer unit with nominal
phase-to-phase winding voltages of 69 kV and 13.2 kV, OA/FA/FA
three-phase ratings of 36/48/60 MVA, five off-load taps (±2
+ neutral position) on the HV winding with a tap step of 2.5%,
a nominal operating frequency of 60 Hz, the high voltage (HV)
windings are connected wye-grounded through a 8.29% impedance
on a 36 MVA, 69 kV base, and the low voltage (LV) windings are
connected delta. The transformer unit has the following test data:
Short-Circuit
Test:
Three-phase load losses at 85°C of 122300 W.
Impedance voltage or winding leakage impedance magnitude of 8.24%
on a 36 MVA apparent power base, 69/13.2 kV voltage base and 85°C.
No-load
or Open Circuit Test:
Three-phase no-load losses at 85°C, 100% (1.0 per unit or
nominal) voltage 24900 W.
Excitation current RMS magnitude of 0.17% (0.0017 per unit) at
85°C, 100% voltage (69/v3 kV) and 36 MVA apparent power base.
This three-phase,
two-winding transformer unit will be used in a generator step-up
(GSU) substation where the generating unit has a rated terminal
voltage of 13.8 kV. The bus voltage base for the HV and LV bus
bars of the GSU substation chosen by the electric utility are
69 kV and 13.8 kV respectively.
Based on
the transformer nameplate data, the short-circuit and no-load
test data the following is known:
HV bus
voltage base: 69 kV
LV bus voltage base: 13.8 kV
HV winding voltage base: 69 kV
LV winding voltage base: 13.2 kV
Number of taps: 5
Tap range, Rmax =1.05 pu (72.45 kV) and Rmin =0.95 pu (65.55
kV) on a 69 kV voltage base
Winding three-phase MVA base (SB1-2): 36 MVA
System three-phase MVA base (SBASE): 100 MVA
Since the
short-circuit and the no-load test data are available, the first
choice for entering the transformer unit data in PSS®E
is recommended to be:
Impedance
code CZ=3, load losses and impedance voltage
Magnetization admittance code CM=2, no-load losses and excitation
current
Winding code CW=1, taps in per unit on a bus voltage base
Control mode: None if the transformer is fit with off-load taps
and Voltage if the transformer is fit with an under-load tap
changer.
All four
steps listed above are recommended to be selected before entering
any electric parameter and tap data in the transformer unit record
in PSS®E.
Given that
tap values for windings 1 and 2 will be entered in per unit on
a bus voltage base (CW=1), and if a user selects the 69 kV as
winding 1 in the transformer model, the tap value t1 and upper
and lower tap limits, Rmax and Rmin, will be specified as:
t1
= 1.0 pu (if the tap is set at its neutral position, i.e., nominal
tap)
Rmax = 1.05 per unit on a 69 kV base
Rmin = 0.95 per unit on a 69 kV base
Winding 2
in this case will be assigned to the 13.2 kV winding and since
the winding voltage base (13.2 kV) does not match the bus voltage
base (13.8 kV) it is necessary to adjust the per unit value of
t2 so that the per unit transformer model is correct. Hence,
t2 = 13.2 kV/13.8 kV = 0.9565 per unit on a 13.8 kV base
Note that 1.0 per unit voltage on a 13.8 kV base (bus system base)
is equivalent to 1.04545 per unit on a 13.2 kV base. In general,
whenever there is a mismatch between the winding voltage base
and the bus voltage base and the winding code is 1, taps expressed
in per unit on bus voltage base must be entered using the expression:
t1 or t2 = winding 1 or winding 2 voltage/ bus voltage base
= (t1 or t2 in pu on winding voltage base)* K
Where K = (winding voltage base/bus voltage base)
If a user selects the 13.2 kV winding as winding 1 and the 69
kV winding as winding 2, then the values for taps t1 and t2, and
tap range Rmax and Rmin will be:
t1 = 0.9565 pu (13.2 kV/13.8 kV) on a 13.8 kV base
Rmax = default (1.1 pu since this winding has no taps)
Rmin = default (0.9 pu since this winding has no taps)
t2 = 1.0 per unit on a 69 kV base
Note that off-nominal tap values for t2 will be manually entered
if the above arrangement is used.
If a user selects the winding code 2 (CW=2), winding 1 is the
69 kV winding and winding 2 is the 13.2 kV winding, the values
for taps t1 and t2, and tap range Rmax and Rmin will be:
t1 = 69 kV (nominal tap position)
Rmax = 72.45 kV
Rmin = 65.55 kV
t2 = 13.2 kV
and if the 13.2 kV windings was selected as winding 1 and the
69 kV winding as winding 2, the values for taps t1 and t2, and
tap range Rmax and Rmin will be:
t1 = 13.2 kV
Rmax = 15.18 kV default value (1.1 pu on a 13.8 bus voltage base)
Rmin = 12.42 kV default value (0.9 pu on a 13.8 bus voltage base)
t2 = 69 kV nominal tap position
In PSS®E
version 31 the new winding code 3 (CW=3) was introduced. If a
user selects the winding code 3 (CW=3), and winding 1 is the 69
kV winding and winding 2 is the 13.2 kV winding, the values for
taps t1, t2 and tap range Rmax and Rmin will be:
t1 = 1.0 pu (if the tap is set at its neutral position, i.e.,
nominal tap)
Rmax = 1.05 per unit on a 69 kV base
Rmin = 0.95 per unit on a 69 kV base
t2 = 1.0 pu (on a 13.2 kV winding voltage base)
and if the 13.2 kV windings was selected as winding 1 and the
69 kV winding as winding 2, the values for taps t1, t2 and tap
range Rmax and Rmin will be:
t1 = 1.0 pu (on a 13.2 kV winding voltage base)
Rmax = 1.1 per unit on a 13.2 kV base
Rmin = 0.95 per unit on a 13.2 kV base
t2 = 1.0 pu (if the tap is set at its neutral position, i.e.,
nominal tap)
The data record for the transformer unit and codes CW=1, CZ=3
and CM=2 is then
The benefit
for entering the transformer model data in this format is that
the user will store in the PSS®E data base the short-circuit
test data, no-load tests and nameplate winding MVA and voltage
ratings. The user will no longer have to keep separate records
for this important data and all the calculations to convert the
test data to winding leakage impedance and magnetization admittance
branch in per unit will be carried out by PSS®E. The only
action required is to change the impedance and admittance codes
to CZ=1 or 2 and CM=1 and PSS®E will show in the data record
for this transformer unit the values in per unit for the winding
leakage impedance and magnetization admittance branch.
For example if the codes used are CW=1, CZ=2 and CM=1, the data
record shown by PSS®E will be
Note that
the equivalent winding resistance and equivalent winding leakage
reactance in per unit on a winding apparent power base and winding
voltage base are:
R12 = r’eq =WCu losses/SB1-2 = 0.1223/36 = 0.003397 pu
and the complex equivalent winding impedance Zeq, nominal in per
unit on a winding apparent power base and winding voltage base
is:
Zeq, nominal = R12 +j X12 = 0.003397 +j 0.08233 pu
and the magnetizing admittance conductance and susceptance in
per unit on a system apparent power base (100 MVA) and winding
1 bus voltage base (69 kV) are:
Gh+e = WNL losses /SBASE = 0.0249/100 = 0.000249 pu
and since
¦IF¦
pu = ¦Ym¦pu * 1.0 pu voltage = ¦Ym¦pu
= 0.0017* (36/100) = 0.000612 pu
then,
The user must keep in mind that the complex magnetizing admittance
in pu on a system apparent power base (100 MVA) and winding 1
bus voltage base (69 kV) is:
Ym = Gh+e –j Bm = 0.000249 –j 0.00559 pu
If the user is interested in finding out the values stored by
PSS®E for the equivalent winding leakage impedance and equivalent
magnetizing branch admittance as per the IEEE Standard Model shown
in Figure 2, they can be found by displaying them in the Report
Window by showing the network data with the IEEE Format Power
Flow Data activity. The result of this procedure is shown below:
Note that the bus data displays the equivalent magnetizing branch
admittance
Ym = 0.0002 –j 0.0006 pu on a 100 MVA and 69 kV base
the branch data displays the equivalent winding leakage impedance
Zeq
Zeq = (t2)2 r’eq +j (t2)2 x’eq
= 0.008634 +j 0.209231 pu on 100 MVA and 69 kV/13.8 kV base
and the transformer turns ratio
t = t1 / t2 = 1.0/0.9565 = 1.0455 pu on 69 kV / 13.8 kV bus voltage
base
The winding connection for this transformer unit is wye-grounded
for HV (69 kV) winding and delta for the LV (13.2 kV) winding.
Since no phase shift angle between the wye and delta connected
windings has been provided, it is safe to assume the ANSI standard
phase shift angle for the wye/delta connection: the HV winding
leads the LV winding by 30°. Thus, the winding 1 angle entry
in PSS®E (relative phase angle between winding 1 and winding
2 with winding 1 leading winding 2) will be:
? +30° if the HV (69 kV) winding is assigned to winding 1
and the LV (13.2 kV) winding is assigned to winding 2
? -30° if the HV (69 kV) winding is assigned to winding 2
and the LV (13.2 kV) winding is assigned to winding 1.
With this
numerical example we have shown the various ways available in
PSS®E to create an electric network model for a two-winding
voltage regulating transformer. The author strongly recommends
the use of the short-circuit and open-circuit test data whenever
possible, since use of this data allows PSS®E users to keep
track of not only the transformer’s winding leakage impedance
and magnetizing admittance data but also of the transformer test
data, all in one single data record.
Download
document as .pdf
| Siemens Energy,
Inc., Power Distribution, T&D Service Solutions
Siemens Power Technologies International
400 State Street | P.O. Box 1058 | Schenectady,
NY 12301-1058
Privacy
& Legal |
|