An Efficient Method for Planning Low Voltage Secondary Distribution
Networks
Synopsis:
The optimal selection of distribution transformer size and low-voltage
(LV) network conductors for a given network configuration poses
various challenges to distribution utilities. This article proposes
an efficient planning methodology to select an optimal combination
of transformer size and the LV network conductor that would minimize
the Life of Asset (LOA) costs while taking into account the voltage
drop and the transformer loading constraints for a period of 30
years including load growth.
In a recent
study for Belize Electricity Limited (BEL), using different combinations
of typical transformer size, triplex service drop conductor and
choice of network configuration, 200 study cases were simulated
in PSS®SINCAL. For each case the cost per kVA was calculated
by dividing the LOA costs by the initial loading capacity for
each transformer. (The initial loading capacity was preferred
over the nominal rating, as it takes into consideration the possible
loading limitations due to voltage drop.) Finally, all network
configurations were generalized based on load density and the
coincident peak load per customer, and cost curves were obtained
for several possible combinations of transformer size and triplex
service drop conductor. The cost versus load density curves were
parameterized using trend line analysis for other load densities
which were not included in the list of study cases. The optimal
combination of transformer size and LV network conductor was found
by locating the combination that minimized the LOA costs for several
given densities.
This method
is described here as applied to the BEL LV distribution network,
but it could be deployed for any LV network configuration. This
article discusses the study conducted for the BEL LV distribution
network using this method, as well as some general results.
BEL
LV Network Generalization:
The characteristics of a sample of 60 distribution transformers
(including 25, 50, 75, and 100 kVA transformers) and their LV
network were statistically analyzed in order to obtain a generalized
BEL LV distribution network configuration. Distance between load
poles, number of customers per load pole, coincident peak load
per customer, and street lighting information were all evaluated.
The findings of the statistical analysis were as follows:
- 50% of
the samples had distance between poles within the range of 110
to 120 ft, and 80% of the samples had distance less than 150
ft. Hence 115 ft and 150 ft were chosen.
- 50% of
the samples had a load per customer less than or equal to 0.5
kVA per customer, and 80% of the samples had 1 kVA per customer.
Hence these values were selected.
- A majority
of the samples showed that there were two customers per pole.
The distance between street lights was chosen to be the same
as the distance between the poles, and their power consumption
was specified as 150 W.
The transformer
ratings chosen for this analysis were: 5, 10, 15, 25, 37.5, 50,
75, and 100 kVA. The LV conductor types were: T 6 Al, T 4 Al,
T 2 Al, 1/0 T Al, 2/0 T Al, 3/0 T Al and 4/0 T Al.
Using the
generalized network criteria and the sets of transformers and
LV conductors, 200 study cases were simulated in PSS®SINCAL
in order to answer the following questions:
- How much
can a transformer be loaded? (An initial loading limit of 70%
of its normal capacity was chosen to give enough margin for
future growth of load connected to that transformer. A 3% voltage
drop limit was set without using the transformer taps.)
- What would
be the total length of the LV network and the peak load losses
for different conductor types?
Figure 1
shows one of the 200 study cases with the transformer –
LV conductor configuration selected for this analysis. Transformer
load was split into four branches (corner location). The first
load pole was assumed to be the transformer pole.

Figure 1 -
Example of the Selected LV Network Configuration in PSS®SINCAL
Cost
Benefit Analysis:
LOA costs were calculated for a period of 30 years and a present
value was estimated using a discount rate of 12%. Figure 2 shows
an example of the cash flow model set up for a study case which
uses a 15 kVA transformer, with a pole distance of 115 ft, with
a load of 1 kVA/customer on a T 6 A1 conductor. For each of LV
network configuration the LOA costs were estimated using the following
criteria:
- Transformer
was installed in year 0 (present year) with 20% of the maximum
initial load. During the 1st and 2nd year, the transformer reaches
60% and 100% of its initial loading, respectively. After the
second year, a load growth of 2% per year was imposed until
the load reaches the capacity equal to the transformer nominal
rating.
- LV network
was installed in 3 years (0, 1 and 2) following the proposed
transformer loading.
- Transformer
core losses and winding losses were obtained using typical data.
Windings losses were adjusted accordingly with the transformer
load in each year.
- LV network
peak losses were obtained from the PSS®SINCAL simulations.
- Annual
energy losses were calculated by applying a loss factor to the
power losses.
- Annual
losses costs were calculated using the average energy cost.

Figure 2
- Example of Cash Flow Model for a Study Case

Figure 3
- Representation of the Study for Selection of Optimal LV Network
Configuration
Conclusion:
All network configurations were generalized based on load density
and cost curves were obtained for several possible combinations
of transformer size and triplex service drop conductors. The results
were depicted in cost curves: cost (US$/kVA) versus load density
(kVA/000 ft) for each transformer size and LV conductor type.
Several comparisons were made between combinations, in order to
filter out the least cost-effective cases.
For the BEL
LV distribution network, the load densities were found to be in
the range of 10 to 30 kVA/000 ft. After the initial comparisons,
the filtered cost curves depicting the results for different load
densities are shown in Figure 4, with the combination of transformer
rating and LV conductor type shown in the legend.
The optimal
combinations were:
- For low
voltages networks with initial load density below 14 kVA/000
ft, a distribution transformer of 25 kVA and T 4 Al conductor.
- For low
voltages networks with initial load density above 14 kVA/000
ft, a distribution transformer of 50 kVA and 2/0 T Al conductor.
The cost
versus load density curves can be parameterized using trend line
analysis for load densities greater than 100 kVA/000 ft.
This efficient
method for planning low voltage secondary distribution networks
has been implemented on the BEL LV distribution network, but it
could be deployed for any LV network configuration.

Figure 4 -
Finalized Cost Curves
Download document
as .pdf
| Siemens Energy,
Inc., Power Distribution, T&D Service Solutions
Siemens Power Technologies International
400 State Street | P.O. Box 1058 | Schenectady,
NY 12301-1058
Privacy
& Legal |
|